4.5 Relay and fieldbus interfaces
ATD4xxW Door Controller for Industrial Applications
142
System Manual, 01/2017, A5E38080677-AB
Connection
The wired RJ45 connectors are connected to the two X1000 Port 1 and X1000 Port 2
terminals.
4.5.4.3
Wiring and connecting relay outputs
Wiring
The PROFINET module has 2 relay outputs (closer contact).
Maximum voltages of 42.0 V (peak value,
≙
29.6 V
rms
in the case of sinusoidal voltage (SELV
according to EN60950-1)) may be applied to the PROFINET module.
Contact rating of the relay outputs:
●
DC max: 30 V DC, 500 mA
●
AC max: 29.6 V AC, 500 mA, sinusoidal (limited due to the fact that only SELV is
permissible on the module)
The matching 4-pole mating connector (PHOENIX MC1.5/4-ST-3.81) with the screw
terminals is delivered along with the module (plugged in).
The pin assignments are: