Diagnostic and maintenance
10.3 Maintenance
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB
275
Alarms
Remedying alarms
Display
Remedy
4
If possible, the system's drive cycle time should be reduced.
5
The new motor type must undergo a learn run. See Section Learn run (Page 29).
P / _
It is imperative that a new learn run be performed during ongoing operation.
y
1)
Communication with the master system is interrupted. The alarm is cleared as soon as
communication is restored.
1)
SIDOOR ATD410W/ATD420W/ATD430W
10.3
Maintenance
The SIDOOR system should be included in the maintenance schedule for the door system
as a whole, and inspected in the course of the maintenance cycles stated in the schedule.
Note
Recommended maintenance cycles provided in the table below may vary according to the
ambient conditions and the stress on the system.
Object
Recommended maintenance interval
DC geared motor
Maintenance-free
SIDOOR control unit
Maintenance-free
Visual inspection of the control unit, the fastening of the
motor mount, the pulley and the mounting brackets for dirt,
damage and proper installation. In addition, an inspection of
the door function is recommended for running or grinding
noises.
1 year
The belt tension should be checked
1 year
With mechanical changes of the system, for example, due to maintenance or wear (friction, dirt, engine replacement, belt
replacement or modification of the general door mechanism), an inspection is recommended for the commissioning pa-
rameters relating to the safety-related settings for forces and energies/velocities.