SIDOOR functions
3.1 Basic functions
ATD4xxW Door Controller for Industrial Applications
System Manual, 01/2017, A5E38080677-AB
37
3.1.2
Force limit for learn run
Description of function
Force that is active during the learn run. The force limit is active in the closing and opening
direction.
The parameter depends on the existing output transmission. The force limit is set to the
maximum value by default.
Note
The force only needs to adjusted for easily-moved door systems and door systems with soft
end stops. A smooth-running door system has a mass to be moved <100 kg and maximum
frictional forces of <20N.
Connection and parameter assignment
The force limit can be configured via the terminal module (
Main menu > General setup >
Special parameters > Force limit for learn run
).
SIDOOR ATD410W / ATD420W / ATD430W
The force limit is set via the parameter p1242. See section Calibration and function
parameters (Page 179) for more on this.