SIDOOR functions
3.1 Basic functions
ATD4xxW Door Controller for Industrial Applications
38
System Manual, 01/2017, A5E38080677-AB
3.1.3
Output transmission
Description of function
For the motors M4, MDG400, MDG400 NMS, M5 and MDG700 NMS, the output
transmission must be configured. The output transmission describes the transformation of
rotational into translational motion. Therefore: The distance [mm] that the door travels with
one revolution [rev] of the transmission output shaft. The output transmission can be
adjusted within the range 0...384 mm/rev. The permitted values are between 88...384
mm/rev. The default value for a newly trained motor type is 0 mm/rev.
MDG400NMS
Mass to be moved
MDG700NMS
Mass to be moved
Output transmis-
sion [mm/rev]
< 200
Output transmis-
sion [mm/rev]
< 250
Output transmis-
sion [mm/rev]
< 300
Output transmis-
sion [mm/rev]
< 384
< 100 kg
< 150 kg
X
X
X
X
< 200 kg
< 350 kg
X
X
X
n.r.
< 300 kg
< 500 kg
X
X
n.r.
n.r.
< 400 kg
< 700 kg
X
n.r.
n.r.
n.r.
n.r. not recommended
Note
For the M4, MDG400 and M5 motors, set default value to 176 mm/rev.
Note
The output transmission should be checked before each learn run and adjusted if necessary.
Note
The determined door width has to be checked after each learn run.
Note
Activation of the learn run via the bus interface (as of V1.09)
The learn run can only be started when a permissible output transmission (parameter p4602)
has been configured. The value for the door width should then be read back via the
parameter r2103 and checked.
Connection and parameter assignment
The drive transmission can be configured via the terminal module (
Main menu > General
setup > Special parameters > Output transmission
).
SIDOOR ATD410W / ATD420W / ATD430W
The output transmission is set via the parameter p4602. See section Calibration and function
parameters (Page 179) for more on this.