Controller
6.6 Connecting terminals and interfaces
ATE500E
60
System Manual, 09/2017, A5E33917696-AD
Installation
Proceed as follows to install the controller:
1.
Drill the holes for the screws as shown in the dimension drawing.
2.
Secure the controller with 4 (M6 x 10) screws.
6.6
Connecting terminals and interfaces
6.6.1
Wiring instructions
NOTICE
Material damage
Only use cables with a temperature range
≥ 85 °C
Table 6- 5
Properties of slots and interfaces
Slot
Name
Maxi-
mum
cable
length
Type
X3
Power supply
< 30 m
Not shielded, supply
X4
24 V voltage output < 30 m
Not shielded, supply see section Voltage output
(Page 65)
X6
Digital inputs
> 30 m
Not shielded, asymmetric data cable
X8
Service interface
< 2 m
Shielded, symmetric and asymmetric data cable