8-2
C7-621 / C7-621 AS-i Control Systems
C79000-G7076-C621-01
The C7 is not designed for field repair. A defective C7 must therefore be
replaced.
To replace a C7, the following requirements must be met:
Hardware
S
Programming device/PC with MPI interface
S
Suitable connecting cable
Development tools
S
STEP 7
S
ProTool or ProTool/Lite
User software (stored outside the C7)
S
User configuration
S
User control program (when data from the C7 CPU can no longer be read)
Follow the steps outlined below:
S
The C7 is removed in the reverse order from that in which it was
installed.
S
Connect a programming device/PC to the MPI interface.
S
Save the user program from the C7-CPU on a programming device/PC
using STEP 7.
If the C7-CPU is defective and the user program can no longer be read,
remove the C7 without attempting to back up the data.
S
The configuration loaded on the C7 cannot be read. This must be
available on a programming device or PC.
As soon as you have a new C7 available, install it as follows:
1. Mechanical and electrical installation is as described in the manual.
2. Connect a programming device/PC to the MPI interface. Set the highest
MPI address.
3. Reset the C7 memory as described.
4. Transfer the previously saved user program from the programming
device/PC with the corresponding data to the C7-CPU (using STEP 7).
5. Download you configuration to the C7 using ProTool/Lite.
6. Start the user program.
Replacing the C7
Requirements
Removal
Installation
Maintenance
Summary of Contents for simatic c7-621
Page 44: ...2 26 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Installing and Preparing the C7 ...
Page 64: ...3 20 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Configuring an MPI Network ...
Page 74: ...5 4 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Attaching a C7 621 AS i ...
Page 82: ...6 8 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 C7 621 Digital I Os ...
Page 100: ...7 18 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 C7 621 Analog I Os ...
Page 101: ...8 1 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Maintenance 8 ...
Page 110: ...A 8 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 General Technical Specifications ...
Page 123: ...Glossary 1 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Glossary ...
Page 136: ...Index 4 C7 621 C7 621 AS i Control Systems C79000 G7076 C621 01 Index ...