Description of the Parameter Data
When you specify time base and factor, you determine how long a timer is
switched on. The length of time the timer is switched on is the product of
time base and factor. Table 7-1 contains sample timer values.
Table 7-1
Examples of timer values
Time Base (msec)
Factor
Switch--On Duration
1
1
1 msec
1
65,535
65.535 sec
(1.092 min)
:
100
1
100 msec
(1.667 min)
100
65,535
6,553.5 sec
(109.225 min)
:
255
1
255 msec
(4.25 min)
255
65,535
16,711.425 sec
(278.542 min)
The default value for time base and factor is 1.
Note
The minimum switch--on duration is 10 msec.
The time base can be specified for a specific timer.
Table 7-2
Setting the time base
Variable:
Time Base
Parameter
Block
Offset
Data Type
Value Range
Timebase_Timer_1
1
2.0
Byte
1 to 255
Timebase_Timer_2
1
3.0
Byte
Timebase_Timer_3
1
4.0
Byte
Timebase_Timer_4
1
5.0
Byte
Timebase_Timer_5
1
6.0
Byte
Timebase_Timer_6
1
7.0
Byte
Timebase_Timer_7
1
8.0
Byte
Timebase_Timer_8
1
9.0
Byte
Time base/
factor
Timer Operating Mode
Summary of Contents for SIMATIC CM35
Page 1: ...SIMATIC Counter Module CM35 Manual Release 06 2000 ...
Page 9: ...vi CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Table of Contents ...
Page 10: ...1 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Product Overview 1 ...
Page 20: ...2 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Function Description 2 ...
Page 23: ...2 4 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Function Description ...
Page 47: ...3 24 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Commissioning ...
Page 48: ...4 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Data Communication with the CM35 4 ...
Page 70: ...5 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Pulse Counter Operating Mode 5 ...
Page 98: ...7 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Timer Operating Mode 7 ...
Page 112: ...8 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Positioning Operating mode 8 ...
Page 131: ...8 20 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Positioning Operating mode ...
Page 133: ...A 2 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Literature ...
Page 134: ...B 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 EC Declaration of Conformity B ...
Page 135: ...B 2 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 EC Declaration of Conformity ...
Page 141: ...Glossary 6 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Glossary ...