3-16
CM35 Counter Module
(4) J31069-D0416-U001-A5-7618
3.3.3
Distributed Integration into the SIMATIC S7
The module is configured as distributed I/O with the HW Config application
of STEP 7. To add a CM35 to an existing project, proceed as shown below.
1. Start the SIMATIC Manager, and open the desired project.
2. In the left--hand portion of the project screen, select the SIMATIC station
from which the DP slave is to be addressed.
3. Select the menu command
Edit > Open Object
.
This opens the HW Config application. This application contains a screen
with the hardware setup of the opened station.
4. If not already done, set up a DP slave. From the
²
Hardware Catalog
²
screen, select an ET 200M with IM 153-2, and place it in a PROFI-
BUS--DP master system.
5. Select the CM35 from the hardware catalog, and place it in the ET 200M.
Based on the position on ET 200M, the required input and output address
areas are automatically assigned to the CM35 and entered in the configura-
tion table. Address gaps in the address areas of the CPU rack are utilized.
The preset address areas can be changed in accordance with certain rules.
For more information on free address assignment, see manual /70/. Proceed
as shown below.
1. In the configuration table, select the line with the CM35, and select the
menu command
Edit > Object Properties
.
2. In the indicated dialog box, open the tab
Addresses
, and enter the desired
start address.
If there are address overlaps with other modules, you will be told this
when you close the dialog box.
3. Leave the dialog box open so that you can make the following settings of
the module’s operating mode.
The operating mode of the CM35 must have already been set during configu-
ration. Proceed as shown below.
1. If not already done, select the line with the CM35 in the configuration
table, and select the menu command
Edit > Object Properties
.
2. In the dialog screen, open the tab
Operating Mode
, select the desired
operating mode, and confirm with
OK
.
For additional preparations before operation, see manual /70/ and user
manual /231/.
Configuration
Module
address
Setting the
operating mode
Commissioning
Commissioning
Summary of Contents for SIMATIC CM35
Page 1: ...SIMATIC Counter Module CM35 Manual Release 06 2000 ...
Page 9: ...vi CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Table of Contents ...
Page 10: ...1 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Product Overview 1 ...
Page 20: ...2 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Function Description 2 ...
Page 23: ...2 4 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Function Description ...
Page 47: ...3 24 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Commissioning ...
Page 48: ...4 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Data Communication with the CM35 4 ...
Page 70: ...5 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Pulse Counter Operating Mode 5 ...
Page 98: ...7 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Timer Operating Mode 7 ...
Page 112: ...8 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Positioning Operating mode 8 ...
Page 131: ...8 20 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Positioning Operating mode ...
Page 133: ...A 2 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Literature ...
Page 134: ...B 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 EC Declaration of Conformity B ...
Page 135: ...B 2 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 EC Declaration of Conformity ...
Page 141: ...Glossary 6 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Glossary ...