5-11
CM35 Counter Module
(4) J31069-D0416-U001-A5-7618
5.2.2
Structure of the Parameter Blocks
Tables 5-9, 5-10 and 5-11 show the data structures of the three parameter
blocks as they must be transferred with SFC55 calls to the CM35.
The first word of the parameter blocks contains the control word. The re-
quired assignment is entered as the initial value in the structures.
For transmission of the data, see chapter 4.2.
Parameter block 1
contains:
S
The comparison or start values for channels 1 to 6
Table 5-9
Parameter block 1
Address
Name
Type
Initial
Value
Commentary
Para_Block_1_Data
STRUCT
+0.0
Control_word
WORD
W#16#11
Parameter block no. 1/counter mode
+2.0
Cmp_Start_Value_Chan_1
WORD
W#16#00
Comparison value/start value, channel 1
+4.0
Cmp_Start_Value_Chan_2
WORD
W#16#00
Comparison value/start value, channel 2
+6.0
Cmp_Start_Value_Chan_3
WORD
W#16#00
Comparison value/start value, channel 3
+8.0
Cmp_Start_Value_Chan_4
WORD
W#16#00
Comparison value/start value, channel 4
+10.0
Cmp_Start_Value_Chan_5
WORD
W#16#00
Comparison value/start value, channel 5
+12.0
Cmp_Start_Value_Chan_6
WORD
W#16#00
Comparison value/start value, channel 6
=14.0
END_STRUCT
Pulse Counter Operating Mode
Summary of Contents for SIMATIC CM35
Page 1: ...SIMATIC Counter Module CM35 Manual Release 06 2000 ...
Page 9: ...vi CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Table of Contents ...
Page 10: ...1 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Product Overview 1 ...
Page 20: ...2 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Function Description 2 ...
Page 23: ...2 4 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Function Description ...
Page 47: ...3 24 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Commissioning ...
Page 48: ...4 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Data Communication with the CM35 4 ...
Page 70: ...5 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Pulse Counter Operating Mode 5 ...
Page 98: ...7 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Timer Operating Mode 7 ...
Page 112: ...8 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Positioning Operating mode 8 ...
Page 131: ...8 20 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Positioning Operating mode ...
Page 133: ...A 2 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Literature ...
Page 134: ...B 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 EC Declaration of Conformity B ...
Page 135: ...B 2 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 EC Declaration of Conformity ...
Page 141: ...Glossary 6 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Glossary ...