5-15
CM35 Counter Module
(4) J31069-D0416-U001-A5-7618
5.4
Controlling the Digital Outputs
You can control the digital outputs of the CM35 as shown below, based on
the parameterization of DO mode.
DO mode:
Automatic:
Note:
A parameterization bit can be used to specify whether
the DO byte is to control the enable
or whether the enable is continuous.
Enable mode =
²²²²
Enable control via DO byte
²²²²
The DO byte is used to enable the output for
control via the counter status.
0: Output disabled
-- The output is not switched on with the start of
counting.
-- A switched on output is forcibly switched off.
1: Output enabled
-- The output is switched on at start of counting.
-- The output is switched off when the comparison
value is reached or counting is stopped.
Enable mode =
²²²²
continuous enable
²²²²
Control via the counter status is continuously enabled for
the outputs. A switched on output can be forcibly switched
off with the DO byte.
0: A switched on output is forcibly switched
off.
(The forced switch--off only affects the current
counting procedure.)
1: No effect
CPU control:
You specify the state of the output with the DO
byte.
0: Switch off output
1: Switch on output
Write the DO byte to the address
²
module start a 0.
²
Note
Control of the digital outputs must be programmed with a word access.
Pulse Counter Operating Mode
Summary of Contents for SIMATIC CM35
Page 1: ...SIMATIC Counter Module CM35 Manual Release 06 2000 ...
Page 9: ...vi CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Table of Contents ...
Page 10: ...1 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Product Overview 1 ...
Page 20: ...2 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Function Description 2 ...
Page 23: ...2 4 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Function Description ...
Page 47: ...3 24 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Commissioning ...
Page 48: ...4 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Data Communication with the CM35 4 ...
Page 70: ...5 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Pulse Counter Operating Mode 5 ...
Page 98: ...7 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Timer Operating Mode 7 ...
Page 112: ...8 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Positioning Operating mode 8 ...
Page 131: ...8 20 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Positioning Operating mode ...
Page 133: ...A 2 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Literature ...
Page 134: ...B 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 EC Declaration of Conformity B ...
Page 135: ...B 2 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 EC Declaration of Conformity ...
Page 141: ...Glossary 6 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Glossary ...