8-14
CM35 Counter Module
(4) J31069-D0416-U001-A5-7618
8.3
Starting and Stopping the Axes
The following conditions must be met before an axis is started for the first
time.
S
The module is parameterized (SF LED is off).
S
The actual value for the axis to be started has been set.
S
A setpoint was written for the axis to be started.
To start the axis, write the start/stop block to address
”module start a 2.”
Note
Before an axis can be started again, it must be stopped with a stop command.
Table 8-5 shows the contents of the start/stop block. The required assign-
ment of the coordination byte is entered in the structure as an initial value.
For a description of the bit assignment of the coordination byte, see chapter
4.3.1.
The write--access of the start/stop block
must
be programmed as a word--
access.
Table 8-5
Start/stop block
Address
Name
Type
Initial Value
Commentary
Start_Stop_Block
STRUCT
+0.0
Start_Axis_1
BOOL
FALSE
01: Start axis 1
+0.1
Stop_Axis_1
BOOL
FALSE
10: Stop axis 1
+0.2
Start_Axis_2
BOOL
FALSE
01: Start axis 2
+0.3
Stop_Axis_2
BOOL
FALSE
10: Stop axis 2
+0.4
Start_Axis_3
BOOL
FALSE
01: Start axis 3
+0.5
Stop_Axis_3
BOOL
FALSE
10: Stop axis 3
+0.6
Start_Axis_4
BOOL
FALSE
01: Start axis 4
+0.7
Stop_Axis_4
BOOL
FALSE
10: Stop axis 4
+1.0
CoordinationByte
BYTE
B#16#84
Start/stop byte enable = 1
C bit = 0/ positioning mode
=2.0
END_STRUCT
Positioning Operating mode
Summary of Contents for SIMATIC CM35
Page 1: ...SIMATIC Counter Module CM35 Manual Release 06 2000 ...
Page 9: ...vi CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Table of Contents ...
Page 10: ...1 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Product Overview 1 ...
Page 20: ...2 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Function Description 2 ...
Page 23: ...2 4 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Function Description ...
Page 47: ...3 24 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Commissioning ...
Page 48: ...4 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Data Communication with the CM35 4 ...
Page 70: ...5 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Pulse Counter Operating Mode 5 ...
Page 98: ...7 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Timer Operating Mode 7 ...
Page 112: ...8 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Positioning Operating mode 8 ...
Page 131: ...8 20 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Positioning Operating mode ...
Page 133: ...A 2 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 Literature ...
Page 134: ...B 1 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 EC Declaration of Conformity B ...
Page 135: ...B 2 CM35 Counter Module 4 J31069 D0416 U001 A5 7618 EC Declaration of Conformity ...