Technical Specifications
8-13
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
Switchover Time in the Case of Redundancy
The switchover time depends on the operating mode and the configuration:
DP Master
System
ET 200M
with
IM 153...
Switchover Time
Configuration
S7-400H
-2AA02
70 ms
Any configuration
-2AB01
30 ms
... without F, FM or HART modules or similar
-2Bx00
30 ms
Any configuration
30 ms
... without F, FM or HART modules or similar
S7 software
-2AA02
70 ms + 2 DP cycles
Any configuration
redundancy
S5-115H/155H
-2AB01
30 ms + 2 DP cycles
... without F, FM or HART modules or similar
S5-115H/155H
-2Bx00
30 ms
Any configuration
30 ms
... without F, FM or HART modules or similar
or
the set response monitoring time, if this is greater than 30 or 70 ms.
Delay Time of the Input and Output Modules
You can find out more in the technical specifications of the modules (see the
Module Specifications) Reference Manual.
8.5
Use of the ET 200M/S7-300 in Zone 2 Hazardous Area
The following sections contain important information in the following languages.
Section
Subject
8.5.1
Einsatz der ET 200M / S7 300 im explosionsgefährdeten Bereich Zone 2
8.5.2
Use of the ET 200M / S7 300 in a Zone 2 Hazardous Area
8.5.3
Utilisation de I’ET 200M / S7 300 dans un environment à risque d’explosion en zone 2
8.5.4
Aplicación de la ET 200M / S7 300 en áreas con peligro de explosión, zona 2
8.5.5
Impiego dell’ET 200M / S7 300 nell’area a pericolo di esplosione zona 2
8.5.6
Gebruik van de ET 200M / S7 300 in het explosief gebied zone 2
8.5.7
Brug af ET 200M / S7 300 i det eksplosionfarlige område zone 2
8.5.8
ET 200M / S7 300: n käyttö räjähdysvaarannetuilla alueilla, vyöhyke 2
8.5.9
Användning av ET 200M / S7 300 i explosionsriskområde zon 2
8.5.10
Uso do ET 200M / S7 300 em área exposta ao perigo de explosão, zona 2
8.5.11
Χρηση τηζ συσΚευηζ
ET 200M / S7 300
σε ...
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com