Parameters/address space
4.2 Parameters
Analog Input Module AI 4xI 2-/4-wire ST (6ES7134-6GD01-0BA1)
1
7
Equipment Manual, 06/2020, A5E03551866-AF
The following parameter settings are possible:
Table 4- 2
Configurable parameters and their defaults (GSD file)
Parameter
Value range
Default
Configura-
tion in RUN
Scope with configuration soft-
ware, e.g. STEP 7 (TIA Portal)
GSD file
PROFINET IO
GSD file
PROFIBUS DP
Diagnostics
No supply voltage L+
•
Disable
•
Enable
Disable
Yes
Module
Module
Diagnostics
Short-circuit to ground
•
Disable
•
Enable
Disable
Yes
Module
Module
Diagnostics
Overflow
•
Disable
•
Enable
Disable
Yes
Module
Module
Diagnostics
Underflow
•
Disable
•
Enable
Disable
Yes
Module
Module
Diagnostics
Wire break
•
Disable
•
Enable
Disable
Yes
Module
Module
Measuring type/range
•
deactivated
•
Current (4-wire transduc-
er) 0..20 mA
•
Current (4-wire transduc-
er) 4..20 mA
•
Current (4-wire transduc-
er) +/-20 mA
•
Current (2-wire transduc-
er) 0..20 mA
•
Current (2-wire transduc-
er) 4..20 mA
Current (4-
wire trans-
ducer)
4..20 mA
Yes
Channel
Channel
Smoothing
•
None
•
weak
•
medium
•
strong
None
Yes
Channel
Channel