Parameters/address space
4.2 Parameters
Analog Input Module AI 4xI 2-/4-wire ST (6ES7134-6GD01-0BA1)
Equipment Manual, 06/2020, A5E03551866-AF
18
Parameter
Value range
Default
Configura-
tion in RUN
Scope with configuration soft-
ware, e.g. STEP 7 (TIA Portal)
GSD file
PROFINET IO
GSD file
PROFIBUS DP
Interference frequency
suppression
2
•
60 Hz
•
50 Hz
1
•
16.6 Hz
50 Hz
Yes
Channel
Module
3
Potential group
•
Use potential group of the
left module (module
plugged into a dark Ba-
seUnit)
•
Enable new potential
group (module plugged in-
to light BaseUnit)
Use potential
group of the
left module
No
Module
Module
1
Interference frequency suppression: Interfering signals at 400 Hz are automatically included in the filtering at 50 Hz.
2
The settings in the "Interference frequency suppression" parameter have a direct effect on the conversion time of the
channel. The analog value is therefore also affected by additionally set filtering via the "Smoothing" parameter.
3
Due to the limited number of parameters of a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD
configuration, the parameter assignment options are restricted. The parameter length of the I/O module is 5 bytes with
PROFIBUS GSD configuration. If necessary, you can set this parameter by using the data record 128, see the appendix
"Parameter data set".
Note
Unused channels
"Disable" unused channels in the parameter assignment to improve the cycle time of the
module.
A disabled channel always returns the value 7FFF
H
.