Error in transferring the data record analog input
Error transferring the data record
The module always checks all values of the data record to be sent. The module applies the
values from the data record only when all values have been transmitted without errors.
The WRREC instruction for writing data records returns corresponding error codes when
errors occur in the STATUS parameter, see also the description of the "STATUS" parameter
in the STEP 7 online help).
The following table shows the module-specific error codes and their meaning for parameter
data record 128.
Error code in STATUS parameter
(hexadecimal)
Meaning
Solution
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
B0
xx
Number of the data record un-
known.
Enter a valid number for the data record.
DF
80
B1
xx
Length of the data record incorrect. Enter a valid value for the data record length.
DF
80
B2
xx
Slot invalid or cannot be accessed.
•
Check the station to determine whether
the module is plugged or pulled.
•
Check the assigned values for the pa-
rameters of the WRREC instruction.
DF
80
E0
xx
Wrong version or error in the
header information.
Correct the version, length and number of
parameter blocks.
DF
80
E1
01
Reserved bit set
Check the parameters of the module.
DF
80
E1
02
Invalid diagnostics enable bit set
for operating mode.
Check the parameters of the module.
DF
80
E1
05
Invalid coding set for measuring
range / measurement type.
Check the parameters of the module.
DF
80
E1
08
Invalid coding set for interference
frequency suppression / integration
time.
Check the parameters of the module.
DF
80
E1
09
Invalid coding for smoothing.
Check the parameters of the module.