Analog Input Module AI 4xI 2-/4-wire ST (6ES7134-6GD01-0BA1)
31
Equipment Manual, 06/2020, A5E03551866-AF
Parameter data record
A
A.1
Dependencies when configuring with GSD file
When configuring the module with a GSD file, remember that the settings of some
parameters are dependent on each other.
Configuring with a PROFINET GSD file
The table lists the properties and their dependencies on the measuring type and measuring
range for PROFINET.
Measuring type Measuring
range
Diagnostics
No supply volt-
age L+
Short-circuit to
M
Overflow
Underflow
Wire break
deactivated
*
*
*
*
*
Current
(4-wire connec-
tion)
0..20 mA
x
-
x
x
-
4..20 mA
x
-
x
x
x
±20 mA
x
-
x
x
-
Current
(2-wire connec-
tion)
0..20 mA
x
x
x
x
-
4..20 mA
x
x
x
x
x
x = Property is allowed, - = Property is not allowed, * = Property is not relevant
Configuring with a PROFIBUS GSD file
The table lists the properties and their dependencies on the measuring type and measuring
range for PROFIBUS.
Measuring type Measuring
range
Diagnostics
No supply voltage
L+
Short-circuit to M
Overflow/
Underflow
Wire break
deactivated
*
*
*
*
Current
(4-wire connec-
tion)
0..20 mA
x
-
x
-
4..20 mA
x
-
x
x
±20 mA
x
-
x
-
Current
(2-wire connec-
tion)
0..20 mA
x
x
x
-
4..20 mA
x
x
x
x
x = Property is allowed, - = Property is not allowed, * = Property is not relevant