FC 45
Function manual, Release 03/2006 , J31069-D0167-U001-A2-7618
4-1
Commissioning
4
1st step: Install ASM in STEP 7
•
ASM 475, 473: The installation program for the ASM 475, 473 must be executed once on
the STEP 7 PC.
•
PROFIBUS-ASM: The GSD file (Siem809F.GSD for ASM 454, 754, 854, 850 or
Siem80B6.GSD for ASM 452) must be linked to the device catalog with HW Config (Tools
> Install new GSD...).
2nd step: Configure hardware in STEP 7
The configuration varies depending on which MOBYASM is being used.
•
ASM 475: Centralized configuration in S7-300
•
ASM 475, 473: Distributed setup with PROFIBUS and ET 200M, ET 200X
•
ASM 452, 454, 754, 854, 850: Distributed setup with PROFIBUS
The following figure shows the placement of the MOBY-ASMs in the hardware catalog.