Error messages and troubleshooting
5.2 Error messages
FC 45
5-4
Function manual, Release 03/2006 , J31069-D0167-U001-A2-7618
Error code
(B#16#..)
Flashing of
ERR LED
Description
04
4x
Error in MDS's memory
The MDS has never been write-accessed or has lost the contents of its
memory due to battery failure.
•
Replace MDS (if battery bit is set).
•
Install MDS with the STG.
•
Reinitialize MSD (see Section "Command parameter settings").
05
5x
Unknown command
FC 45 is sending an uninterpretable command to the MOBY-ASM.
•
Command_DB contains invalid command parameters.
•
The command_DB was overwritten by the user
•
The MDS reported an address error.
MOBY F:
•
Read/write area is protected by password.
•
FFT command can only be used when ANW check is off.
06
6x
Field interference on write/read device
The write/read device is receiving interference from its environment.
•
External interference field. The field of interference can be verified
with the "inductive field indicator" of the STG.
•
The distance between two write/read devices is too small and does
not correspond to the configuration guidelines
•
The connecting cable to the write/read device is defective or too
long or does not comply with the specification
•
MOBY U: MDS has left the field during communication.
•
MOBY U: Communication between write/read device and MDS was
terminated by interference (e.g., person/foreign body moving
between write/read device and MDS).
07
7x
Too many transmit errors
The MDS was not able to correctly receive the command or the write
data from the ASM even after several attempts.
•
The MDS is positioned exactly on the boundary of the transmission
window.
•
Data transmission to the MDS is being affected by external
interference.
MOBY F: Another MDS was detected in the field while the command
was being processed.
08
8x
CRC sending error
•
The receiver monitor has detected at least one fault during
transmission.
–
Cause same as error B#16#06.
•
MDS signaling CRC error frequently.
–
The MDS is positioned exactly on the boundary of the
write/read device.
–
The hardware of the MDS and/or write/read device is defective.
09
9x
Only during initialization: CRC error during acknowledgment receipt
from MDS
•
Cause same as error B#16#06.