Error messages and troubleshooting
5.2 Error messages
FC 45
5-6
Function manual, Release 03/2006 , J31069-D0167-U001-A2-7618
Error code
(B#16#..)
Flashing of
ERR LED
Description
10
16x
Next command not possible or not permitted
•
ASM is running without MDS control (MDS_control = 0,1).
•
ASM has already received a Next command.
•
ASM / write/read device doesn't recognize NEXT command.
11
–
Short circuit or overload of the 24 V outputs (DQ, error code, presence)
•
The affected output is turned off.
•
All outputs are turned off when total overload occurs.
•
A reset can only be performed by turning the 24 V voltage off and
on again.
•
Then start init_run.
12
18x
Internal ASM communication error
•
Connector contact problem on the ASM
•
Defective ASM hardware
–
Return ASM for repair
•
Start init_run command after error correction.
13
19x
ASM / write/read device U does not have enough buffer to store the
command intermediately.
14
20x
Internal ASM / write/read device error
•
Program sequence error on the ASM
•
Turn power of ASM off and on again.
•
Start init_run command after error correction.
•
MOBY U: Watchdog errror on write/read device.
15
21x
Wrong parameterization of the ASM/SLG
•
Check INPUT parameters in UDT 10
•
Check parameters in HW Config
•
RESET command is parameterized incorrectly.
•
After a start-up, the ASM has still not received an init_run.
16
22x
The FC command cannot be executed with the ASM parameters on
PROFIBUS.
•
Length of the input/output areas too small for the cyclic I/O word.
Did you use the right GSD file?
•
FC command (e.g., read) with too much user data (data length >
233 bytes).
17
23x
Communication error between FC 45 and MOBY-ASM.
Handshake error
•
Params_DB (UDT 10) of this ASM station is being overwritten by
other parts of the program
•
Check parameters of MOBY-ASM in UDT 10
•
Check FC 45 command which caused this error
•
Start init_run command after error correction.
18
–
An error has occurred which must be acknowledged with an init_run.
•
A temporary short circuit has occurred on PROFIBUS.
•
The RESET command is faulty.
•
Start init_run command after error correction.
•
Check parameters ASM_address, ASM_channel, and
MOBY_mode.