Communication Management for SIMATIC S7
7-4
TP 070 Equipment Manual
Release 03/00
Table 7-1
Network parameter
Network parameter
Explanation
TP address
Address of the TP 070
Protocol
The protocol profile used in the network configuration.
Set
MPI or DP here.
Baud rate
The baud rate at which communication takes place
over the network.
S7-200 address
Address of the S7 module (CPU) to which the TP 070
is connected.
HSA
Highest Station Address; this must be identical
throughout the whole network configuration.
Data types supported
The data types listed in table 7-2 are available for the configuration of tags.
Table 7-2
Data types available
Data types supported for S7–200
Data type
Addressed by
Format
Tag
V
BYTE, INT, WORD,
DINT, DWORD, REAL,
BOOL, STRING
Input
I
BYTE, INT, WORD,
DINT, DWORD, REAL,
BOOL, STRING
Output
Q
BYTE, INT, WORD,
DINT, DWORD, REAL,
BOOL, STRING
Flag
M
BYTE, INT, WORD,
DINT, DWORD, REAL,
BOOL, STRING
Timer
T
TIMER
Counter
C
COUNTER
Summary of Contents for SIMATIC HMI TP 070
Page 14: ...Functionality 2 2 TP 070 Equipment Manual Release03 00 ...
Page 18: ...Commissioning 3 4 TP 070 Equipment Manual Release03 00 ...
Page 34: ...System Settings 6 6 TP 070 Equipment Manual Release03 00 ...
Page 40: ...Communication Management for SIMATIC S7 7 6 TP 070 Equipment Manual Release03 00 ...
Page 54: ...Maintenance Upkeep 10 2 TP 070 Equipment Manual Release03 00 ...
Page 56: ...Operating System Update 11 2 TP 070 Equipment Manual Release03 00 ...
Page 57: ...APPENDIX A Technical Data B Interface Assignment C ESD Guidelines D SIMATIC HMI Documentation ...
Page 58: ...APPENDIX K 2 TP 070 Equipment Manual Release03 00 ...
Page 64: ...Technical Data A 6 TP 070 Equipment Manual Release03 00 ...
Page 66: ...Interface Assignment B 2 TP 070 Equipment Manual Release03 00 ...