Installing and connecting the device
3.3 Connecting the device
Mobile Client900WXN
Operating Instructions, 04/2015, A5E35883103-AB
39
●
Route the equipotential bonding conductor and data cables in parallel with minimum
clearance between them.
Note
Cable shielding is not suitable for equipotential bonding. Always use the prescribed
equipotential bonding conductors. Ensure there is sufficient cable cross-section.
Otherwise, there is a risk that interface components will be damaged or destroyed.
Connection graphic
The figure below shows how to connect the equipotential bonding of the connection boxes to
the equipotential busbars.
①
Ground connection
②
Equipotential bonding conductor, cross-section 1.5 mm
2
③
Equipotential busbar
④
Ethernet cable
⑤
Equipotential bonding conductor, cross-
section ≥ 16
mm
2
⑥
Parallel routing of the equipotential bonding conductor and data cable
⑦
Cable clamp
⑧
Control cabinet
⑨
PROFINET cable