2.
Measure approximately 10 cm of cable.
3.
Place the cable in the stripping tool.
4.
Clamp the cable with the stripping tool by pressing the lever fully forward.
5.
To strip the cable, turn the stripping tool in the direction of the arrow.
6.
Keeping it closed, pull the stripping tool with the jacket and shield remnants off the end of the cable.
Note
If a wire was damaged during stripping, you will need to cut off the section of
cable and repeat steps 2 to 5.
7.
If necessary, remove any cable remnants by hand. Cut off the inner cable spacer as completely as possible.
8.
Insert the cable in the cable manager.
With a 4-pair cable, the lever
Should only be pressed
forward as far as the second
from the last position.