Certification
6.1.9 Other Approvals
6.1.9
Other Approvals
This device meets the requirements of the following additional standards:
•
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
•
IEC 61850-3
Communications Networks and Systems for Power Utility Automation – Part 3:
General Requirements
•
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
•
NEMA TS-2
Traffic Controller Assemblies with NTCIP Requirements
6.2
EMC and Environmental Type Tests
The RUGGEDCOM RS400 has passed the following EMC and environmental tests.
IEC 61850-3 EMC Type Tests
Test
Description
Test Levels
Severity
Levels
Enclosure
Contact
±8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
±15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Signal Ports
±4 kV at 2.5 kHz
DC Power Ports
±4 kV
4
AC Power Ports
±4 kV
4
IEC 61000-4-4
Burst (Fast
Transient)
Earth
Ground Ports
±4 kV
4
Signal Ports
±4 kV Line-to-Earth,
±2 kV Line-to-Line
4
DC Power Ports
±2 kV Line-to-Earth,
±1 kV Line-to-Line
3
IEC 61000-4-5
Surge
AC Power Ports
±4 kV Line-to-Earth,
±2 kV Line-to-Line
4
Signal Ports
10 V
3
D.C Power Ports
10 V
3
AC Power Ports
10 V
3
IEC 61000-4-6
Induced
(Conducted) RFI
Earth
Ground Ports
10 V
3
36
RUGGEDCOM RS400