Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
100% for 0.05 s
Signal Ports 2 kV (Failsafe Relay Output)
DC Power
Ports
2 kV or 2.8kV DC
Dielectric Strength
AC Power
Ports
2 kV
Signal Ports 5 kV (Failsafe Relay Output)
DC Power
Ports
5 kV
IEC
60255-27
HV Impulse
AC Power
Ports
5 kV
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RST916C meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
Test
Description
Test Levels
Enclosure Contact
± 8 kV
IEEE 1613
ESD
Enclosure Air
± 15 kV
IEEE 1613
Radiated RFI
Enclosure Ports
35 V/m
Signal Ports
± 4 kV @ 2.5 kHz, 5 kHz
DC Power Ports
± 4 kV @ 2.5 kHz, 5 kHz
AC Power Ports
± 4 kV @ 2.5 kHz, 5 kHz
IEEE 1613
Fast
Transient
Earth Ground Ports
± 4 kV
Signal Ports
2.5 kV Common
Mode @ 1 MHz
IEEE 1613
Oscillatory
DC Power Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
Signal Ports
5 kV (Failsafe Relay)
DC Power Ports
5 kV
IEEE 1613
HV Impulse
AC Power Ports
5 kV
Signal Ports
2 kV (Failsafe Relay)
DC Power Ports
2.8 kVDC or 2 kV
IEEE 1613
Dielectric
Strength
AC Power Ports
2 kV
IEEE 1613.1
IEC 61000-4-10
Damped
Oscillating
Magnetic
Field
Enclosure Ports
100 A/m for 1 s (100
kHz and 1 MHz)
RUGGEDCOM RST916C
Installation Manual, 04/2021, C79000-G8976-1490-03
39