Certification
6.2 EMC and Environmental Type Tests
EMC Type Tests
Test
Description
Test Levels
Severity
Levels
Enclosure
Contact
± 8 kV
4
IEC
61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC
61000-4-3
Radiated RFI
Enclosure
Ports
20 V/m
Signal Ports
± 4 kV @ 2.5 kHz, 5 kHz
4
DC Power
Ports
± 4 kV @ 2.5 kHz, 5 kHz
4
AC Power
Ports
± 4 kV @ 2.5 kHz, 5 kHz
4
IEC
61000-4-4
Burst (Fast Transient)
Earth
Ground Ports
± 4 kV @ 2.5 kHz, 5 kHz
4
Signal Ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
DC Power
Ports
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
3
IEC
61000-4-5
Surge
AC Power
Ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
Signal Ports
10 V
3
DC Power
Ports
10 V
3
AC Power
Ports
10 V
3
IEC
61000-4-6
Induced (Conducted) RFI
Earth
Ground Ports
10 V
3
IEC
61000-4-8
Magnetic Field
Enclosure
Ports
100 A/m Continuous
1000 A/m for 1 s
IEC
61000-4-9
Pulse Magnetic Field
Enclosure
Ports
300 A/m
4
IEC
61000-4-11
Voltage Dips and Interrupts
AC Power
Ports
30% for 0.5 Cycles
60% for 5 Cycles
100% for 250 Cycles
Signal Ports
30 V Continuous
300 V for 1 s
4
IEC
61000-4-16
Mains Frequency Voltage
DC Power
Ports
30 V Continuous
300 V for 1 s
4
IEC
61000-4-17
Ripple on DC Power Supply
DC Power
Ports
15%
4
IEC
61000-4-18
Damped Oscillatory Wave
Slow
Damped
2.5 kV Common
100 kHz or 1 MHz
3
IEC
61000-4-29
Voltage Dips and Interrupts
DC Power
Ports
30% for 0.1 s
60% for 0.1 s
38
RUGGEDCOM RST916P
Installation Manual, 04/2021, C79000-G8976-1489-01