Installing and putting a TIM into operation
5.4 Options for attachment and settings of the TIM 3 and TIM 4 variants
SINAUT ST7 Station control system - System Manual
System Manual, 05/2007, C79000-G8976-C178-06
181
Note
The transmission speeds 1200 and 2400 bps are suitable for lines whose bandwidth is
limited to the normal voice band (300 Hz ... 3400 Hz). This is typically the case with lines
leased from public telephone companies. For the MD2 modem, there is an approval from the
German Telekom for connection to transmission paths with analog connection points (2-
wire) and 3.1 kHz effective bandwidth (300 Hz ... 3400 Hz).
Table 5-18 Settings on the 10-pin DIL switch of the TIM 32
Setting on
DIL switch
Meaning
2))
21
Normal mode
This mode must be selected when the MD2 is used as an integrated
modem in the TIM (for example TIM 32).
2))
21
Test mode: Test send
2))
21
Test mode: Test receive
2))
21
Test mode: Test f baud
2))
21
Test mode: Test f L
2))
21
Test mode: Test f H
2))
21
Character format: Message consisting of a series of asynchronous
characters, each 11-bit (1 start bit, 8 data bits, 1 parity bit, 1 stop bit).
This is the standard setting for sending SINAUT ST1 or SINAUT ST7
messages. In this case, message format FT 1.2, based on 11-bit
asynchronous characters is normally used for transmitting over
dedicated lines.