Installing and putting a TIM into operation
5.4 Options for attachment and settings of the TIM 3 and TIM 4 variants
SINAUT ST7 Station control system - System Manual
192
System Manual, 05/2007, C79000-G8976-C178-06
Note
The following description of the possible settings on the integrated MD3 modem apply only
to the TIM 33 (6NH7800-3AA30) with a hardware version ≥ 6.
Settings with the DIL switches accessible from above
On the integrated MD3 modem, the metering pulse filter must be selected and the basic
setting for dial-up mode made. These settings are made using a 4-pin and a 10-pin DIL
switch. The 10-pin DIL switch, SW2 is located directly on the top housing grill. The 4-pin DIL
switch, SW1, can also be reached from above through the housing grill, however it is located
deeper within the housing and may therefore be more difficult recognize. To set this switch,
you require a long, thin tool, for example a small screwdriver or a toothpick.
The DIL switches have the following functions:
● 4-pin DIL switch SW1
– Metering pulse filter
at 12 kHz or at 16 kHz
● 10-pin DIL switch SW2
– Setting one of the 8 standard dialing profiles
(only profile 0 or 7 is used on the integrated MD3 modem)
– Data format 11 bits or 10 bits
– Tone or pulse dialing
– Reset function
– Loudspeaker ON or OFF
– Line adjustment with 600 ohms or Zr (frequency-dependent)
Note
Only standard dialing profile 0 can be set on the integrated MD3 modem. Standard
dialing profiles 1 through 6 (V.25bis profiles) are not supported by the integrated MD3
modem.