Installing and putting a SINAUT modem into operation
6.8 Installing and putting a SINAUT MD2, MD3, MD4 modem into operation
SINAUT ST7 Station control system - System Manual
System Manual, 05/2007, C79000-G8976-C178-06
313
Table 6-50 Permitted ambient temperature for SINAUT modems
Installation position
Permitted ambient temperature
MDx
Horizontal
0 to 60 °C
MDx
Vertical
0 to 40 °C
Dimensions for installing SINAUT modems
Table 6-51 Dimensions for installing SINAUT modems
Module
Module width
Module height
Max. depth
Modem module
MD2, MD3 and MD4
80 mm
125 mm
120 mm or 180 mm
with open front panel
6.8.4
Connecting to the power supply
WARNING
Connecting the modem module to a live power supply can damage the module. Connect
the modem to the power supply only when the power supply is off.
WARNING
The power for the device (24 V DC) must be generated as a safe extra low voltage. This
means it must be a SELV (Safety Extra Low Voltage) or PELV (Protective Extra Low
Voltage) according to DIN VDE 0100 Part 410 (IEC 60364-4-41).