Introduction to the SINAUT ST7 system
2.3 SINAUT TIM communication modules
SINAUT ST7 Station control system - System Manual
34
System Manual, 05/2007, C79000-G8976-C178-06
– Over the MPI interface of this CPU with other CPUs and control center PCs (ST7cc,
ST7sc) connected over the MPI bus
– With other TIMs in this rack
● Message memory for up to 10,000 data messages
The following figure shows one of the TIM 3 variants.
Figure 2-5
SINAUT TIM 3 transmission module
Note
The TIM 3 cannot be combined with a CPU 315-2PN/DP, CPU 317, CPU 318 or CPU 319.
With these CPU types, a TIM 4 must be used that is connected to the CPU over the MPI
interface or an Ethernet TIM.
The following TIM 3 variants are available:
TIM 32
TIM 3 with integrated modem MD2 (dedicated line)
TIM 33
TIM 3 with integrated modem MD3 (analog telephone network)
TIM 34
TIM 3 with integrated modem MD4 (ISDN)