Introduction to the SINAUT ST7 system
2.3 SINAUT TIM communication modules
SINAUT ST7 Station control system - System Manual
36
System Manual, 05/2007, C79000-G8976-C178-06
2.3.10
Technical specifications of the TIM 3 variants
Technical specifications of the TIM 32
TIM 32
General
Interfaces
•
Attachment to dedicated line
•
Connection to power supply
•
RJ-12
•
4-pin terminal strip
Power supply
24 V DC; min. 20.4 V; max. 28.8 V
Current consumption
•
From backplane bus
•
From 24 V DC
•
60 mA
•
300 mA
Power loss
7.5 W
Permitted ambient conditions
•
Operating temperature
•
Transport/storage temperature
•
Relative humidity
•
0 °C t60°C
•
-40 °C t70 °C
•
Max. 95 % at +25 °C
Construction
•
Module format
•
Dimensions (W x H x D) in mm
•
Weight
•
Compact module for S7-300, double width
•
80 x 125 x 120
•
Approx. 300 g
Degree of protection
IP 20
Configuration
•
Software for PG
•
Software for CPU (optional)
•
Storage of TIM configuration data
•
SINAUT ST7 configuration software
for PG
•
SINAUT TD7 block library for CPU
•
on internal TIM flash memory
TIM can be operated in the role
•
Station
•
Node station
•
Master station
•
Yes
•
Yes
•
Yes
No. of TIM 32 modules per S7-300
Several, number depends on the communication
resources of the S7-300 CPU
Local communication in the rack of an S7-300
•
Over backplane bus with the S7-300-CPU
•
Over backplane bus with other TIMs in the
rack
•
Over MPI port of the S7-300-CPU
2)
with other
CPUs, TIMs, and/or PCs
•
Possible using TD7onCPU
1)
•
Possible
•
Possible over TD7onCPU (for S7-300 and
S7-400) and S7 communication (for
ST7cc/ST7sc and TIMs)
Work memory required on the S7 CPU
At least 20 KB; actual requirements depend on
the amounts of data and range of functions
Message memory on TIM
•
Number of messages
•
Buffered
•
Approx. 10,000 messages
•
No