Introduction to the SINAUT ST7 system
2.3 SINAUT TIM communication modules
SINAUT ST7 Station control system - System Manual
38
System Manual, 05/2007, C79000-G8976-C178-06
TIM 32
Lower / upper keying frequency
•
At 1200 bps
•
At 2400 bps
•
At 9600 and 19200 bps
•
1300 Hz / 2100 Hz
•
2400 Hz / 3300 Hz
•
20800 Hz / 33600 Hz
Floating optical relay output
•
Max. connected voltage
•
Max. permitted permanent current
•
Max. R
on
•
60 V AC/DC
•
400 mA
•
3 ohms
Surge withstand capability
U
1.2/50
to DIN VDE 0804
between supply circuit and
•
FSK remote line circuits
•
Optical relay output
•
2.5 kV
•
2.5 kV
Compatible with SINAUT modems
•
MD100
•
MD124
•
At 1200 bps
•
At 1200, 2400 and 19200 bps
Approvals
EU approval CE 0682 X
1)
The use of TD7onCPU over backplane bus is possible with the following CPU types:
All variants of the CPU 313C, CPU 314 and CPU 314C;
the CPU 315-2 DP and the CPU 315F-2 DP;
all variants of the C7 devices C7-633, C7-635 and C7-636
2)
The MPI ports of the S7-300-CPU can be used with the following CPU types:
All variants of the CPU 312, CPU 312C, CPU 314 and CPU 314C;
the CPU 315-2 DP and the CPU 315F-2 DP
Technical specifications of the TIM 33
TIM 33
General
Interfaces
•
Attachment to telephone network
•
Connection to power supply
•
RJ-12
•
4-pin terminal strip
Power supply
24 V DC; min. 20.4 V; max. 28.8 V
Current consumption
•
From backplane bus
•
From 24 V DC
•
60 mA
•
400 mA
Power loss
9.9 W
Permitted ambient conditions
•
Operating temperature
•
Transport/storage temperature
•
Relative humidity
•
0 °C t60 °C
•
-40 °C t70 °C
•
Max. 95 % at +25 °C