Introduction to the SINAUT ST7 system
2.3 SINAUT TIM communication modules
SINAUT ST7 Station control system - System Manual
52
System Manual, 05/2007, C79000-G8976-C178-06
Technical specifications of the TIM 44 / 44D
TIM 44 / TIM 44D
General
Interfaces
•
Attachment to ISDN network
•
Connection to external data transmission
device
•
MPI bus
•
DCF77 antenna (TIM 44D)
•
Connection to power supply
•
RJ-12
•
9-pin D-sub male connector, RS-232 can be
switched to RS-485
•
9-pin D-sub female connector
•
BNC socket (over supplied DCF77 adapter
cable)
•
4-pin terminal strip
Transmission rate over the RS-232/RS-485
interface
50 to 38,400 bps
Power supply
24 V DC; min. 20.4 V; max. 28.8 V
Current consumption
•
From backplane bus
•
From 24 V DC
•
60 mA (only when the TIM is used as a CP in
an S7-300 rack)
•
500 mA
Power loss
12.3 W
Permitted ambient conditions
•
Operating temperature
•
Transport/storage temperature
•
Relative humidity
•
0 °C t60 °C
•
-40 °C t70 °C
•
Max. 95 % at +25 °C
Construction
•
Module format
•
Dimensions (W x H x D) in mm
•
Weight
•
Compact module for S7-300, double width
•
80 x 125 x 120
•
Approx. 300 g
Degree of protection
IP 20
Configuration
•
Software for PG
•
Software for CPU (optional)
•
Storage of TIM configuration data
•
SINAUT ST7 configuration software
for PG
•
SINAUT TD7 block library for CPU
•
on internal TIM flash memory
TIM can be operated in the role
•
Station
•
Node station
•
Master station
•
Yes
•
Yes
•
Yes
Number of TIM 44/44D modules per S7-CPU or
PC
Several, number depends on the communication
resources of the S7-CPU or of the PC
Local communication in the rack of an S7-300
•
Over backplane bus with the S7-300-CPU
•
Over backplane bus with other TIMs in the
rack
•
Over MPI port of the S7-300-CPU
2)
with other
CPUs, TIMs, and/or PCs
•
Possible using TD7onCPU
1)
•
Possible
•
Possible over TD7onCPU (for S7-300 and
S7-400) and S7 communication (for
ST7cc/ST7sc and TIMs)