System modifications during redundant operation
10.6 Re-parameterization of a module
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB
181
10.6.2
Step 1: Editing parameters offline
Starting situation
The fault-tolerant system is operating in redundant system mode.
Procedure
1.
Edit the module parameters offline in HW Config.
2.
Compile the new hardware configuration, but do not load it into the target system just yet.
Result
The modified hardware configuration is in the PG/ES. The target system continues operation
with the old configuration in redundant system mode.
10.6.3
Step 2: Stopping the reserve CPU
Starting situation
The fault-tolerant system is operating in redundant system mode.
Procedure
1.
For CPU access protection with password: In SIMATIC Manager, select a CPU of the
fault-tolerant system, then select
"PLC > Access Rights > Setup" from the menu. Enter the CPU access password.
2.
In SIMATIC Manager, select a CPU of the fault-tolerant system, then select "PLC >
Operating Mode" from the menu.
3.
In the "Operating Mode" dialog box, select the standby CPU and click "Stop".
Result
The standby CPU switches to STOP mode, the master CPU remains in RUN mode, the
fault-tolerant system works in single mode. The one-sided I/O of the standby CPU is no
longer addressed.