Supplementary information
15.14 Other options for connecting redundant I/Os
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB
297
Monitoring times during link-up and update
Note
If you have made I/O modules redundant and have taken account of this in your program,
you may need to add an overhead to the calculated monitoring times so that no bumps occur
at output modules (in HW Config -> Properties CPU -> H Parameter).
An overhead is only required if you operate modules from the following table as redundant
modules.
Table 15- 8 For the monitoring times with redundant I/O
Module type
Overhead in ms
ET200M: Standard output modules
2
ET200M: HART output modules
10
ET200M: F-output modules
50
Follow the steps below:
●
Calculate the overhead from the table. If you use several module types from the table
redundantly, apply the largest overhead.
●
Add this to all of the monitoring times calculated so far.