The figure below shows the parameters included in the calculation of the MTBF of a system.
Figure A-2 MTBF
Requirements
This analysis assumes the following conditions:
●
The failure rate of all components and all calculations is based on an average
temperature of 40 °C.
●
The system installation and configuration is free of errors.
●
All replacement parts are available locally, in order to prevent extended repair times due
to missing spare parts. This keeps the component MDT down to a minimum.
●
The MDT of individual components is 4 h. The system's MDT is calculated based on the
MDT of the individual components plus the system structure.
●
The MTBF of the components meets the following standards:
–
SN 29500
This standard is compliant with MIL–HDBK 217–F.
–
IEC 60050
–
IEC 61709
●
The calculations are made using the diagnostic coverage of each component.
●
A CCF factor between 0.2% and 2% is assumed, depending on the system configuration.