System modifications during redundant operation
10.6 Re-parameterization of a module
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB
183
10.6.5
Step 4: Switching to CPU with modified configuration
Starting situation
The modified hardware configuration is downloaded to the reserve CPU.
Procedure
1.
In SIMATIC Manager, select a CPU of the fault-tolerant system, then select "PLC >
Operating Mode" from the menu.
2.
In the "Operating Mode" dialog box, click the "Switch to..." button.
3.
In the "Switch" dialog box, select the "with altered configuration" option and click the
"Switch" button.
4.
Acknowledge the prompt for confirmation with "OK".
Result
The reserve CPU links up, is updated and becomes the master. The previous master CPU
switches to STOP mode, the fault-tolerant system continues operating in single mode.
Reaction of the I/O
Type of I/O
One-sided I/O of previous
master CPU
One-sided I/O of new master
CPU
Switched I/O
I/O modules
are no longer addressed by the
CPU.
Output modules output the
configured substitute or holding
values.
are given new parameter set-
tings
1)
and updated by the
CPU.
continue operation without
interruption.
1) Central modules are also reset first. Output modules briefly output 0 during this time (instead of the configured substitute
or hold values).
Reaction to monitoring timeout
The update is canceled and no change of master takes place if one of the monitored times
exceeds the configured maximum. The fault-tolerant system remains in single mode with the
previous master CPU and, assuming certain conditions are met, attempts the master
changeover later. For additional information, refer to section Time monitoring (Page 123).
Where the values for the monitoring times in the CPUs differ, the higher values always apply.