Diagnostics for
Diagnostics tool
Called via
OS fault - preparing diagnostics
Only to support experts
You can find information on this in the section
"OS fault - preparing diagnostics (Page 84)".
Status PCS 7 Web Server
Internet Explorer: http://<server_address>.sta‐
tus.html
8.14
Diagnostics for the BATCH stations
Overview
Diagnostics for
Diagnostics tool
Called via
Operating capability of all BATCH com‐
ponents and communication connec‐
tions
Maintenance station (Page 90) The Maintenance Station is an operator station
that is specially configured for use in diagnostics.
The Maintenance Station has to be configured.
Additional information is available in the docu‐
mentation
Process Control System PCS 7; Main‐
tenance Station
Status of the BATCH server
Taskbar
Status of master
Taskbar
Status of the standby server (partner
server)
Taskbar
Status of the batches
Status display at order folder
Order folder
Additional information is available in the docu‐
mentation
Process Control System PCS 7; SI‐
MATIC BATCH
8.15
Diagnostics for the Route Control stations
Overview
Diagnostics for
Diagnostics tool
Called via
Operating capability of all SIMAT‐
IC Route Control components
and communication connections
The Maintenance Station is an operator station that
is specially configured for use in diagnostics.
The Maintenance Station has to be configured.
Additional information is available in the documenta‐
tion
Process Control System PCS 7; Maintenance
Station
Status of redundant servers
Status icons in the Route Control
Taskbar
Established connections to SI‐
MATIC stations
NetPro: Online view > Select CPU: PLC > Activate
Connection Status
Diagnostics in PCS 7
8.15 Diagnostics for the Route Control stations
Service Support and Diagnostics (V8.2)
Service Manual, 03/2016, A5E36200111-AA
103