You can now update the second IM in the redundant system. Each IM must be updated
separately.
Note
Direct firmware update of both IMs in a redundant system via PROFIBUS DP
With IM 153-2 firmware as of V4.x, it is possible to update the firmware of both IMs during
ongoing operation in redundant mode. The update is supported by STEP 7 and has no effect
on the running application. The firmware in a redundant system is updated (directly) from the
programming device / PC via PROFIBUS DP.
Requirement
● PG/PC with PROFIBUS interface (e.g. CP 5611)
● Programming device / PC is connected directly with PROFIBUS DP
● STEP 7 version on the programming device / PC: as of STEP 7 V5.4
● The update file for the firmware update is available on the programming device / PC.
● The H system is error-free and in redundant mode.
Procedure
1. In the SIMATIC Manager, select the menu command Options > Set PG/PC Interface...".
2. Select the PROFIBUS interface.
3. Click the "Properties" button and set the interface according to the configured bus
parameters.
4. Select the menu command PLC > Display Accessible Nodes... in SIMATIC Manager.
5. Select the station containing the IM you want to update.
6. Select the shortcut menu command Update Firmware.
The "Update Firmware" dialog box opens. Both IMs are displayed with order number,
current firmware version and bus address.
7. Select the firmware file to be loaded to the IMs.
8. Click "Execute". The firmware is updated.
Note
There is a momentary loss of redundancy for the station following the update of the respective
IMs due to their restart.
Updating the identifier
Note
After the firmware update of the IM has been successfully completed, update the identifier of
the firmware version. You can find information on this in the section "Hardware Updates
(Page 33)".