Configuring / Programming
9.7 Programming
PN/BACnet LINK
76
Operating Instructions, 10/2017, A5E39895543-AA
Name diagram of the created PLC tags
Module/
Submodule
IO data
Name diagram
Data
type
S7 address
mnemonic
BACnet client Prefix: <LinkName>.<ClientSubmoduleName>
ClientStatus
<Prefix>.ClientStatus
Bool
%I<
ByteAdr
>.0
ClientControl
<Prefix>.ClientControl
Bool
%Q<
ByteAdr
>.0
BACnet server Prefix: <LinkName>.<ServerSubmoduleName>
ServerStatus
<
Prefix
>.ServerStatus
Byte
%IB<
ByteAdr
>
ServerControl
<
Prefix
>.ServerControl
Byte
%QB<
ByteAdr
>
Binary input
<
Prefix
>.<IOObjectName>
Bool
%Q<
ByteAdr
>.0
<
Prefix
>.<IOObjectName>.OUT_OF_SERVICE
Bool
%Q<
ByteAdr
>.7
Binary output
<
Prefix
>.<IOObjectName>
Bool
%I<
ByteAdr
>.0
<
Prefix
>.<IOObjectName>.OUT_OF_SERVICE
Bool
%Q<
ByteAdr
>.7
Analog input
<
Prefix
>.<IOObjectName>
Real
%QD<
ByteAdr
>
<
Prefix
>.<IOObjectName>.OUT_OF_SERVICE
Bool
%Q<
ByteAdr
>.7
Analog output
<
Prefix
>.<IOObjectName>
Real
%ID<
ByteAdr
>
<
Prefix
>.<IOObjectName>.OUT_OF_SERVICE
Bool
%Q<
ByteAdr
>.7
BACnet device
Prefix: <LinkName>.<BACnetDeviceModuleName>
Binary input
<
Prefix
>.<IOObjectRefName>
Bool
%I<
ByteAdr
>.0
<
Prefix
>.<IOObjectRefName >.IN_ALARM
Bool
%I<
ByteAdr
>.4
<
Prefix
>.<IOObjectRefName >.FAULT
Bool
%I<
ByteAdr
>.5
<
Prefix
>.<IOObjectRefName >.OVERRIDDEN
Bool
%I<
ByteAdr
>.6
<
Prefix
>.<IOObjectRefName >.OUT_OF_SERVICE
Bool
%I<
ByteAdr
>.7
Binary output
<
Prefix
>.<IOObjectRefName >
Bool
%Q<
ByteAdr
>.0
<
Prefix
>.<IOObjectRefName >.IN_ALARM
Bool
%I<
ByteAdr
>.4
<
Prefix
>.<IOObjectRefName >.FAULT
Bool
%I<
ByteAdr
>.5
<
Prefix
>.<IOObjectRefName >.OVERRIDDEN
Bool
%I<
ByteAdr
>.6
<
Prefix
>.<IOObjectRefName >.OUT_OF_SERVICE
Bool
%I<
ByteAdr
>.7
Analog input
<
Prefix
>.<IOObjectRefName >
Real
%ID<
ByteAdr
>
<
Prefix
>.<IOObjectRefName >.IN_ALARM
Bool
%I<
ByteAdr
>.4
<
Prefix
>.<IOObjectRefName >.FAULT
Bool
%I<
ByteAdr
>.5
<
Prefix
>.<IOObjectRefName >.OVERRIDDEN
Bool
%I<
ByteAdr
>.6
<
Prefix
>.<IOObjectRefName >.OUT_OF_SERVICE
Bool
%I<
ByteAdr
>.7
Analog output
<
Prefix
>.<IOObjectRefName >
Real
%QD<
ByteAdr
>
<
Prefix
>.<IOObjectRefName >.IN_ALARM
Bool
%I<
ByteAdr
>.4
<
Prefix
>.<IOObjectRefName >.FAULT
Bool
%I<
ByteAdr
>.5
<
Prefix
>.<IOObjectRefName >.OVERRIDDEN
Bool
%I<
ByteAdr
>.6
<
Prefix
>.<IOObjectRefName >.OUT_OF_SERVICE
Bool
%I<
ByteAdr
>.7
I/Q: Input/output bit address
IB/QB: Input/output byte address
ID/QD: Input/output double word address
Summary of Contents for SIMATIC PN/BACnet LINK
Page 1: ......