Assembling
2
2.1
Assembly rules
Mounting position
You can mount the PN/PN coupler in any position. Please note that the maximum ambient
temperature for horizontal mounting positions is 60 °C while that for all other positions is
40 °C.
You will find more information on operating conditions in Appendix Technical data (Page 79).
Open component
The PN/PN coupler is an open component. In other words, you may only set it up in
enclosures, cabinets or electrical service rooms. These should only be accessible by means
of a key or a special tool. Only trained or authorized personnel may have access to the
enclosures, cabinets or electrical service rooms.
Technical setup
Mount the PN/PN coupler on a DIN rail (7.5 mm and 15 mm). Ensure a space of 40 mm both
above and below the module for unimpeded assembly.
2.2
Assembling the PN/PN coupler
Components required
●
PN/PN coupler
●
Mounting rail:
–
DIN rail (7.5 mm) or
–
DIN rail (15 mm)
The order numbers for the components can be found in Appendix Order numbers and
accessories (Page 89).