Service and maintenance
12.4 Factory defaults
SIMATIC RF185C, RF186C, RF188C, RF186CI, RF188CI
172
Operating Instructions, 04/2020, C79000-G8976-C512-03
12.4.2
Reset the factory setting with SINEC PNI
Requirement
The reader is connected to the PC via Industrial Ethernet or PROFINET.
Procedure
Proceed as follows to reset all settings to the factory settings using SINEC PNI:
1.
Start SINEC PNI.
2.
Click on the "Start network scan" button on the toolbar.
Reaction: The network is scanned for connected devices and all recognized devices are
displayed in the device list.
3.
Select the desired reader in the device list.
4.
Click on the "Reset device" button on the toolbar.
Result: The reader is reset to the original factory settings.
Note that restoring to factory settings assigns the factory-set IP address to the reader.
Because the IP address is discarded, it is possible that the connection between the WBM
and browser is lost. You can only recognize when the restore process is completed based on
the "RUN" LED. After restoring, the reader is restarted. The reader is ready for operation
when the "RUN" LED is lit/flashes green.
After restarting the reader, you may need to assign a new IP address or a new device name
to the reader.