Service and maintenance
12.2 Error messages
SIMATIC RF650R/RF680R/RF685R
Configuration Manual, 03/2018, C79000-G8976-C386-06
297
XML/
LED
(hex)
OPC UA
status
AutoId
status
AutoId
text
Error description
0xA5 good
19
RF_COMMUNICATION_
ERROR
The selected frequency is not enabled.
0xA6 good
19
RF_COMMUNICATION_
ERROR
The carrier signal is not activated.
0xA7 good
9
MULTIPLE_
IDENTIFIERS
There is more than one transponder in the transmission
window.
0xA8 good
19
RF_COMMUNICATION_
ERROR
General radio protocol error
0x41
good
20
DEVICE_FAULT
Fault in power supply
The power supply is very close to the low limit.
0x43
good
20
DEVICE_FAULT
Antenna errors
•
The antenna or the antenna cable is defective.
•
Error in the connection to the reader; the reader is not
answering (in PROFIBUS operation).
–
The cable between the communications module
and reader is wired incorrectly or there is a cable
break
–
The 24 V supply voltage is not connected or is
turned off or has failed briefly
–
Automatic fuse on the communications module
has blown
–
Hardware defective
–
Another reader is in the vicinity and is active
–
There is a reflecting metal surface in the vicinity
that is disrupting the antenna field
–
Execute "init_run" after correcting the error
0x46
OpcUa_
BadInva-
lidState
--
--
The command is not permitted in this status or is not
supported.
Possible cause:
•
"INIT" was chained.
•
Command repetition was started without "Presence
mode".
0xC1 good
18
INVALID_
CONFIGURATION
The specified tag field of the transponder is unknown.
0xCA good
1
MISC_ERROR_
TOTAL
General error
0xCB OpcUa_
BadOutOf
Range /
OpcUa_
Bad
Configura-
tion
Error
--
--
No or bad configuration data/parameters were trans-
ferred.
Possible cause:
•
You are accessing a read point that is not configured.