RF660R reader
5.1 Description
RF600
System Manual, 09/2005 Edition, J31069 D0171-U001-A0-7618,
5-9
5.1.7
Grounding connection
A low-impedance earth connection ensures that interference signals generated, for example,
by external power supply cables or signal cables are safely discharged to earth.
Required tool for protective earth terminal: TORX T20 screwdriver
Ground connection/protective earth terminal
The protective earth terminal (M4 threads) (1) on
the device (large surface, large-area contact) has
to be connected with the protective earth
conductor of the plant or the cabinet in which the
reader is to be installed.
The minimum conductor cross-section may not
be less than 2.5 mm2.