S5-115U Manual
Introduction to STEP 5
•
OB6 cannot itself be interrupted.
•
OB6 can interrupt the cyclic or time-controlled program but not a running interrupt program
(OB2 to 5)! If the clock prompt expires while an interrupt OB is being processed, the OB6 call is
delayed as a result.
•
The OB6 call can also be delayed in the following circumstances:
-
If integral FBs are used
-
If the integral clock has been initialized
-
If PG/OP functions are pending
-
If SINEC L1 is connected
-
If a computer link or ASCII driver have been activated
or
-
If time-controlled OBs have been programmed.
Table 9-1 in Chapter 9 (Interrupt Processing) contains the time by which the OB6 call is
delayed.
7.4.5
Handling Programming Errors and PLC Malfunctions
It is possible to determine the response of the CPU to errors and malfunctions using error response
OBs.
The operation which triggers the timeout, substitution or transfer errors can be replaced by
calling the relevant error response OB. Appropriate responses to errors can be programmed in
these OBs. If only "BE" is programmed there, no response follows, i.e. the PLC does
not go to
STOP. If no relevant OB exists, the CPU jumps to the STOP mode.
OB19
Response when an unloaded block is called
In OB19, you can program the response of the CPU when an unloaded block is called.
Example:
The CPU is to go to STOP when an unloaded block is called:
OB19
STL
Explanation
:STP
:BE
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
STOP statement
If OB19 has not been programmed, the control program continues execution (no re-
sponse) immediately after the jump statement (the destination of the jump does not
exist!)
OB23
Response to timeout in the case of direct I/O access
The following operations can result in timeout: L PB; LPW; T PB; T PW; LIR; TIR; TNB.
The timeout (QVZ) error occurs if a module fails to acknowledge within 160
µ
s of being
accessed. The cause may be a program error, a defect in the module or the removal of
the module during the RUN mode. The operating system stores the absolute module
address at which the QVZ occurred in system data word 103 (EACE
H
) and calls OB23. If
OB23 does not exist, the CPU goes to STOP with QVZ.
EWA 4NEB 811 6130-02b
7-23
Summary of Contents for SIMATIC S5-115U
Page 6: ...EWA 4NEB 811 6130 02b ...
Page 16: ...EWA 4NEB 811 6130 02b ...
Page 18: ...EWA 4NEB 811 6130 02b ...
Page 26: ......
Page 62: ...EWA 4NEB 811 6130 02b ...
Page 64: ...EWA 4NEB 811 6130 02b ...
Page 67: ......
Page 74: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 114: ...EWA 4NEB 811 6130 02b ...
Page 280: ...EWA 4NEB 811 6130 02b ...
Page 372: ...EWA 4NEB 811 6130 02b ...
Page 432: ...EWA 4NEB 811 6130 02b ...
Page 442: ......
Page 528: ...EWA 4NEB 811 6130 02b ...
Page 590: ......
Page 591: ......
Page 592: ......
Page 593: ......
Page 594: ......
Page 600: ...EWA 4NEB 811 6130 02b ...
Page 602: ...EWA 4NEB 811 6130 02b ...
Page 604: ...EWA 4NEB 811 6130 02b ...
Page 624: ...EWA 4NEB 811 6130 02b ...
Page 632: ...EWA 4NEB 811 6130 02b ...
Page 644: ...EWA 4NEB 811 6130 02b ...
Page 646: ...EWA 4NEB 811 6130 02b ...
Page 652: ...EWA 4NEB 811 6130 02b ...
Page 654: ...EWA 4NEB 811 6130 02b ...
Page 660: ...EWA 4NEB 811 6130 02b ...
Page 662: ...EWA 4NEB 811 6130 02b ...
Page 666: ...EWA 4NEB 811 6130 02b ...
Page 668: ...EWA 4NEB 811 6130 02b ...
Page 674: ...EWA 4NEB 811 6130 02b ...