Technical Description
S5-115U Manual
Programmable Restart Delay at Cold Restart and After Power Restore
If you want to delay checking the module configuration because, for example, switching the
voltage to a remotely connected EU is delayed, you must modify system data word 126 (EAFC
H
) in
one of the following ways:
•
With the DISPL ADDR programmer function (only permissible when the CPU is in the STOP
mode!)
•
With STEP 5 operations in the control program (only in FBs).
In any event, the restart delay will only become effective after the next POWER OFF POWER ON
transition and remains effective until the next modification to this system data word. After
Overall Reset, the default applies (0000
H
, i.e. no delay). One unit in system data word 126 corre-
sponds to a restart delay of 1 ms; the longest possible delay is 65535 ms (FFFF
H
).
Example:
Programming a restart delay of approximately one minute
STL FB98
Explanation
:L KH EA60
Restart delay of 60,000 ms (1 minute)
:T BS 126
:BE
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a
Note
If no backup battery has been inserted in the power supply module (or if the inserted
battery is defective) and the control program is stored on an E(E)PROM submodule,
the restart will be delayed by approximately one second.
Restart
While the CPU is in RESTART, the following applies:
•
The fault LEDs are dark; the RUN, STOP and BASP LEDs light up
•
All output modules are disabled (outputs show signal "0")
•
The PII is not yet updated; evaluation of the inputs is only possible with direct I/O access
(L PY../L PW..)
Example:
L PW 0
T IW 0
A I 0.0
:
•
Scan time monitoring is inactive
•
The relevant RESTART OB is processed (in the case of manual cold restart of OB21, in the case
of automatic cold restart of OB22 - if the mode selector is at "RN")
•
Timers are processed
•
Interrupt OBs (OB2 to OB6) and timed-interrupt OBs (OB10 to OB13) are only processed if the
interrupts are explicitly enabled (RA operation).
2-16
EWA 4NEB 811 6130-02b
Summary of Contents for SIMATIC S5-115U
Page 6: ...EWA 4NEB 811 6130 02b ...
Page 16: ...EWA 4NEB 811 6130 02b ...
Page 18: ...EWA 4NEB 811 6130 02b ...
Page 26: ......
Page 62: ...EWA 4NEB 811 6130 02b ...
Page 64: ...EWA 4NEB 811 6130 02b ...
Page 67: ......
Page 74: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 97: ......
Page 98: ......
Page 99: ......
Page 114: ...EWA 4NEB 811 6130 02b ...
Page 280: ...EWA 4NEB 811 6130 02b ...
Page 372: ...EWA 4NEB 811 6130 02b ...
Page 432: ...EWA 4NEB 811 6130 02b ...
Page 442: ......
Page 528: ...EWA 4NEB 811 6130 02b ...
Page 590: ......
Page 591: ......
Page 592: ......
Page 593: ......
Page 594: ......
Page 600: ...EWA 4NEB 811 6130 02b ...
Page 602: ...EWA 4NEB 811 6130 02b ...
Page 604: ...EWA 4NEB 811 6130 02b ...
Page 624: ...EWA 4NEB 811 6130 02b ...
Page 632: ...EWA 4NEB 811 6130 02b ...
Page 644: ...EWA 4NEB 811 6130 02b ...
Page 646: ...EWA 4NEB 811 6130 02b ...
Page 652: ...EWA 4NEB 811 6130 02b ...
Page 654: ...EWA 4NEB 811 6130 02b ...
Page 660: ...EWA 4NEB 811 6130 02b ...
Page 662: ...EWA 4NEB 811 6130 02b ...
Page 666: ...EWA 4NEB 811 6130 02b ...
Page 668: ...EWA 4NEB 811 6130 02b ...
Page 674: ...EWA 4NEB 811 6130 02b ...