5-16
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
2. Enter the value in the “KH” format:
Structure of Parameterization Frame:
7 6
5
4
3
2
1
0
Parameterization frame
Baud rate of I/O bus
Evaluation of diagnostic data from modules
with diagnostics capability
Result when pulling or plugging–in modules
or when bus module defective
0 0 0 0
Mode of IM 318–C
Figure 5-5 Structure of Parameterization Frame
The values of the bits in the parameterization frame are explained in the fol-
lowing table (default is always “0”):
Table 5-7
Meaning of the Parameters in the Parameterization Frame
Bit
Value
Meaning
Bit 0:
Result when pulling or plugging
i
d l
h
b
d l
0
All outputs are set to “0” in the case of a fault. The
ET 200U(DP Standard) station does not enter STOP mode.
in modules or when bus module
defective
1
The ET 200U(DP Standard) interrupts the “shifting” on
the I/O bus. The ET 200U(DP Standard) reads in the
plugged–in modules again and continues the data transfer
on the basis of the current values.
When “shifting” is interrupted, the output values are re-
tained.
Bit 1:
Evaluation of diagnostic data
f
d l
ith di
ti
0
Diagnostic data from modules with diagnostics capability
are not evaluated.
from modules with diagnostics
capability
1
If modules with diagnostics capability are plugged–in, the
diagnostic data are evaluated.
Bit 2:
Mode of the IM 318–C
0
IM 318–C acts as ET 200U(DP Standard), ET 200U(FMS)
or ET 200U in a mixed configuration.
1
IM 318–C is operated as combi slave.
Bit 3:
B
d
t
f I/O b
0
The I/O bus is not operated in Slow Mode.
Baud rate of I/O bus
1
The I/O bus is operated in Slow Mode.
3. Confirm your input of the parameterization frame by pressing <F6>
(ENTER).
ET 200U(DP Standard): Address Assignm.,Starting–Up, Diagnosing Faults Using COM ET 200