5-30
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
5.3.2 Using COM ET 200 to Diagnose Problems
The COM ET 200 software provides the DIAGNOSTICS screen for diagnos-
tics functions.
The following are prerequisites for using the diagnostics function:
You have a programmer with a CP 5410 S5–DOS/ST programmer–bus
interface connected to the SINEC L2–DP bus.
You indicated “Programmer connected to the bus: Y” in the ET 200 SYS-
TEM PARAMETERS screen.
1. Press <F6> (DIAGNOSE) in the FUNCTIONS screen to call up the
DIAGNOSTICS: OVERVIEW screen.
Result: The “DIAGNOSTICS: OVERVIEW” screen appears.
Channel
diagnost.
EXIT
F2
F3
F4
F5
F6
F7
F8
F1
Station number: 1
Program file selected: C: TEST@@ET.200
SIMATIC S5 / COM ET 200
DIAGNOSTICS: OVERVIEW
Station type: DP Master / V x.y
System name: Test system 4712
Station number:
3 5 14 15 26 37 48 123
Figure 5-10
DIAGNOSTICS: OVERVIEW Screen
COM ET 200 displays the following:
The station number and the system name of the master station
The firmware version of the IM 308–B interface module (in the master
station)
The numbers of the stations for which diagnostics data is available
2. Press <F1> (DIAGNOSE INDIVID.)
ET 200U(DP Standard): Address Assignm.,Starting–Up, Diagnosing Faults Using COM ET 200