6-38
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
3. Select “Edit – I/O – CI editor” to call up the “CI editor” screen and then
enter the relevant values for the “8DI” and the “8DO”:
OK
SELECT
F
1
F
2
F
3
F
4
F
5
F
6
F
7
F
8
DELETE
INSERT
CP Type: CP5431
CI Editor
Source: C:QENGLHW
L2 station address:
1
Output area:
Input area:
from OY 0
to
OY 255
from OY 0
to OY 255
Rem.add. DSAP Passwd Index Vartype I/O Input/output area M Mon.int.
4 20 30 UN08 I OY 100 OY 100 1 3000
4 21 33 UN08 O OY 100 OY 100 1 3000
Figure 6-5 “CI Editor” Screen
Result: You have now configured the I/O modules for cyclic data com-
munications.
You can now access the I/O modules via load/transfer operations, such as
“L IB 100” or “T QB 100”, in the STEP 5 program.
Prerequisite: Use job number 210 to call up the “SEND” FB and job num-
ber 211 to call up the “RECEIVE” FB.
ET 200U(DP Standard/FMS): Modes, Settings and Comm. Capabilities of IM 318–C