8-2
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
8.1
General Technical Specifications
Climatic Environmental Conditions
Temperature Operating
S
horizontal design
S
vertical design
0 ... + 60
°
C
(32 to 140
_
F)
0 ... + 40
°
C
(32 to 140
_
F)(Air–intake
temperature, measured on
the underside of the mo-
dule)
Temperature Nonoperating – 40 ... + 70
°
C
(
*
40 to
)
150
_
F)
Temperature change
S
operating
S
nonoperating
max. 10
°
C/h (50
_
F/h)
max. 20
°
C/h
(68
_
F/h)
Relative humidity to DIN
40040
15 to 95 % (indoor), non-
condensing
Atmospheric pressure
S
operating
S
nonoperating
860 to 1060 hPa
660 to 1060 hPa
Pollutants
S
SO
2
S
H
2
S
v
0.5 ppm (rel. humidity
v
60 %, noncondensing)
v
0.1 ppm (rel. humidity
v
60 %, noncondensing)
Mechanical Environmental Conditions
Vibration to IEC 68–2–6
tested with
S
10
v
f
t
57 Hz
S
57
v
f
t
150 Hz
S
mode of vibration
S
period of vibration
S
operating conditions
S
constant amplitude
0.075 mm
S
constant acceleration
1g
S
frequency sweeps with
a sweep rate of 1 oc-
tave/min.
S
10 frequency sweeps
per axis in each of the
3 perpendicular axes
S
to IEC 1131–2
Shock to IEC 68–2–27
S
type of shock
S
shock intensity
S
direction of shock
S
semisinusoidal
S
peak value 15 g,
time 11 ms
S
2 shocks in each of the
3 perpendicular axes
Free–fall to IEC 68–2–31
S
tested with
height of fall 50 mm
Electromagnetic Compatibility (EMC) / Noise Immu-
nity
Electrostatic discharge test
to IEC 801–2
S
test voltage
Discharge on all parts that
are accessible to the opera-
tor during normal opera-
tion
2.5 kV
(Rel.humidity 30 to 95%)
Radiated electromagnetic
field test to IEC 801–3
Field strength 3 V/m
Fast transient burst to IEC
801–4, class III
Power supply modules
S
supply voltage
24 V DC
S
supply voltage
115 /230 V AC
S
analog input/output
modules
S
digitaligital input/out-
put modules
for V = 24 V
for V > 24 V
S
Communications inter-
face
1 kV
2 kV
1 kV
1 kV
2 kV
1 kV
Degree of Protection to IEC/VDE
Degree of protection to
IEC 529
S
type
S
class
IP 20
I to IEC 536
Insulation rating
S
between electrically in-
dependent circuits and
with circuits connected
to a central grounding
point
S
between all circuits
and a central groun-
ding point
to DIN VDE 0160
(05.1988)
to DIN VDE 0160
(05.1988)
Test voltage for a rated
voltage V
inputs
of the cir-
cuits (AC/DC)
V
input
= 0 to 50 V
V
input
= 50 to 125 V
V
input
= 125 to 250 V
SINe, 50 Hz
500 V
1250 V
1500 V
Module Spectrum