8-26
ET 200U Distributed I/O Station
EWA 4NEB 812 6087–02b
8.7
Digital Output Modules
Digital Output Module 4
24 V DC / 0.5 A
(6ES5 440–8MA11)
pr93a028
Technical Specifications
Address identifier for ET 200U
DP Siemens
DP Standard
048
8DQ or 032
Number of outputs
Galvanic isolation
in groups of
4
no
4
Load voltage L+
rated value
permissible range
(including ripple)
value when t < 0.5 s
24 V DC
20 to 30 V
35 V
Output current for “1” signal
rated value
permissible range
lamp load
0.5 A
5 to 500 mA
max. 5 W
Residual current at “0” signal
max. 0.5 mA
Output voltage
at “1” signal
max. L+ (– 1.2 V)
Short–circuit protection
short–circuit protected
output with autom
switch on when the
short–circuit does not
exist any more
Fault LED (red)
short–circuit / no sup-
ply L+
Error diagnostics
possible
Voltage induced on circuit in-
terruption (internal) limited to
–15 V
Switching frequency
resistive load
inductive load
max. 100 Hz
max. 2 Hz
Total permissible current of
outputs
2 A
Driving of digital input
possible
Module Spectrum